Positive Pressure Type Explosion-proof Analytical Houseintroduction

Positive Pressure Type Explosion-proof Analytical HouseAlso Known AsPositive Pressure Explosion-proofShelter,Explosion-proof Positive PressureShelter,Explosion-proof Positive PressureRoom。ByRoomStructure、SelfControlsystem、StationLinesystem、Alarm System、Userpower distributionsystem、Positive PressureArea、SlowPunchAreacomposition;

Positive Pressure Type Explosion-proof Analytical HouseAdvancedStationmethodForventilationType, Namely InvincibleAreaDeterminationContinuityPower SupplyStation,Positive PressureRoomDomesticInstallationcomponent的IndustryOperatingHeatQualityUpWithStationLinewithRun,haveVeryBrilliant的Heat DissipationEnergy-savingEffect。

Positive Pressure Type Explosion-proof Analytical HousePrinciple

Positive Pressure Type Explosion-proof Analytical Houseinautomaticcontrolsystem的controlNext,IntroduceProtectionGas,Positive PressureRoomDomesticpressureHigher thanPositive PressureRoomOverseas的pressure,DescribeCostMicroPositive Pressure safetySmallEnvironment,therebyHinderPrevent了flammablePerformancedangerousGas And DustEntryPositive PressureRoomDomestic,guaranteeRoomDomesticInstallationOrdinaryInstrumentTable And ElectricAppliancecomponent safetyoperation。

Positive Pressure Type Explosion-proof Analytical House

Positive Pressure Type Explosion-proof Analytical HouseparameterTable

Positive Pressure Type Explosion-proof Analytical HouseparameterTable

Positive Pressure Type Explosion-proof Analytical HouseConfiguration List

Positive Pressure Type Explosion-proof Analytical HouseConfiguration List

Positive Pressure Type Explosion-proof Analytical HouseFineEnergy-saving

Positive Pressure Type Explosion-proof Analytical HouseSystemOperatingprocessFineEnergy-saving And Explosion-proof analysis shelterGreaterStructureRelatedSame。The difference lies in the addition of the pressurized automatic control system, pressurized compartment, and buffer compartment.。

Positive PressureArea And SlowPunchArea

RoomStructureByPositive PressureArea And SlowPunchAreacomposition,Positive PressureAreaDomesticInstallationUserpower distributionsystemcomponent And PartSelfControlsystem的explosion-proofcomponent;SlowPunchAreaUsersComeForsolutionOperatepersonnelAdvancedOutputRoomAreapressureProtectionSupport。

Positive Pressureautomaticcontrolsystem

Positive PressureautomaticcontrolsystemmainlycompleteautomaticChangeStation、RepairStation、UndervoltageAlarm、LowPressureLinkedLock、ChangeStationLinkedLockEtc.seriesfunction。When the pressure falls below the specified value (50Pa), an audible and visual alarm is triggered to remind the user to check the intake pressure and leakage points; when the pressure falls below the specified value (25Pa), the user power supply entering the pressurized room is automatically cut off.。The alarm system is the same as that of structurally explosion-proof types, but without an exhaust system, relying on incoming clean air to purge and ventilate the pressurized chamber.。Public power distribution and instrument power distribution are configured according to customer requirements.。

Positive Pressure Type Explosion-proof Analytical HouseCommissioning

CommissioningFrontInspect

SelfControlsystemPartmainlyByPositive Pressure Explosion-proofController、Explosion-proof distribution box、explosion-proofAlarmLight、explosion-proof ExtentSwitch、differencePressureSensorEtc.composition。Check whether each component is intact and undamaged, whether explosion-proof performance is affected, whether wiring is correct (connect control power: AC220V), and whether the manual valve is open.。Commissioning can only proceed after everything is confirmed normal.。

Commissioningmethod

Air SourceFacilityBrilliantAfter-sales, Completely PunchingOpen"AdvancedStationmanualValve",meanwhileAccordingNextSelfControlexplosion-proofBox的"Start"AccordingKey,AdvancedStationElectromagneticValvePunchingOpen,OpenStart PouringDesignWhen10ClassBell,EntryChangeStationstatestate,systemautomaticDetectionCabinetDomesticpressureValue。After purging for 10 minutes, if the pressure value inside the cabinet is greater than 50Pa, the system enters normal operation state, and the purging solenoid valve closes. At this time, the bypass throttle valve supplies air to the positive-pressure cabinet (as preset), stabilizing the pressure inside the cabinet between 100-200Pa (if the pressure is unstable, adjust the throttle valve's lower adjustment nut to adjust the inlet opening until the pressure value stabilizes at a fixed value). At this point, non-explosion-proof instruments can be powered on for operation. During use, if the pressure exceeds 400Pa, the pressure-limiting valve opens to keep the pressure inside the cabinet within the normal working range, preventing high pressure.If the pressure decreases and falls below 50Pa, the system enters an under-pressure alarm state, and the explosion-proof audible and visual alarm light will alarm; if the pressure continues to drop below 25Pa, the system enters a power-off interlock state, and the contactor inside the cabinet automatically cuts off the power to non-explosion-proof instruments in the positive-pressure room, while the explosion-proof audible and visual alarm light continues to alarm. This is the low-pressure protection and electrical interlock process. The alarm sound can be canceled by pressing the "silence" button, but the system state will not change; only changing the pressure can change the system state.If the entire cabinet needs to be powered off for maintenance, all running loads, the positive-pressure room power distribution system, and the automatic control system should be stopped in sequence, and the "inlet manual valve" should be closed. After about 5 minutes, when the pressure inside the positive-pressure room is fully released, the cabinet cover can be opened. For restart, repeat the above steps and perform purging to avoid the risk of flammable gas remaining in the positive-pressure room before power is supplied. The automatic control system box is equipped with a "debug" button, which can be used for full-cabinet power-on commissioning when there is no air source input to the cabinet but the surrounding gas environment is safe.note: Ensure that the surrounding gas environment is safe before using the "debug" button.!!!

CommissioningPrecautions

FoundationProductOutputFactoryWhen,VariousparameteralreadyEquipmentStableBrilliant,Strictly ProhibitUserExpertSelfGreaterModificationparameter。During commissioning, users should pay attention to the unobstructed flow of instruments, automatic control lines, and sampling gas pipelines.。

Positive Pressure Type Explosion-proof Analytical HouseFAQ

1. Positive Pressure Type Explosion-proof Analytical Houseprice?

Answer: The price is determined by parameter configuration; the regular price ranges from approximately 100,000 to 150,000 RMB.。

2. What to do if you cannot commission the pressurized explosion-proof analysis shelter??

Answer: Henan Hualong Electric provides free on-site technical guidance services, guiding and assisting customers with installation, commissioning, and trial operation.。

3. How to choose a manufacturer for explosion-proof analysis shelters??

Answer: Well-known manufacturers in the industry include Henan Hualong and Huarong Explosion-Proof; when selecting a manufacturer, check whether the explosion-proof certificates and qualifications are complete; products without certificates are considered unlicensed products with safety hazards.。DetailsLearn,RecommendRead:Explosion-proof CertificationCheckConsultAlgorithm